200/5A 32mm Current Transformer | Class 1.0 Metering CT
| Accuracy Class | Class 1.0 |
|---|---|
| Secondary Current | 5A |
| VA Rating | 2.5–15 VA |
| Application | Metering & Current Measurement |
200/5A Encapsulated Square CT with 32×10mm Window: Specifications and Uses
The 200/5A Encapsulated Square CT steps a primary current of 200A down to a 5A secondary signal (40:1) for ammeters, energy meters, power analysers and protection relays. A balanced three-phase load of 200A at 415V is about 144 kVA, so this rating suits circuits up to that size. It is supplied in Class 1.0 with a rated burden of 2.5-15 VA and a 32×10mm window.
Encapsulated Square CT Construction and 32×10mm Window
The square CT sits in a flame-retardant polycarbonate casing with a rectangular 32×10mm window, designed to slide over flat copper or aluminium busbars. A bar up to 32mm wide and 10mm thick, including any insulation sleeve, fits through the window. Mounting base brackets and busbar clamping accessories keep the unit firm against vibration.
Where a 200/5A CT Is Used
At 200A, this CT is commonly specified for outgoing feeders, motor control centre feeders, workshop and floor distribution boards, and sub-metering of individual loads. Panel builders and switchgear OEMs choose the encapsulated square CT when the panel needs this rating in a 32×10mm window.
Accuracy, Burden and Testing
The CT delivers Class 1.0 accuracy within its rated burden of 2.5-15 VA, with marked primary (P1-P2) and secondary (S1-S2) terminals for correct polarity. The insulation level is 0.72 kV with a 3 kV, 1-minute power-frequency test. Each unit is routine tested for ratio error, phase displacement, insulation resistance and polarity before dispatch.
Supply and Dispatch
We manufacture at our factory in Mangol Puri, New Delhi, and dispatch across India with a GST invoice. For a quotation, send the ratio and quantity on WhatsApp +91 78360 04040 or use the Request Quote button.
What does a 200/5A ratio mean?
A 200/5A CT reduces a primary current of 200A to 5A on the secondary, a ratio of 40:1. Set the meter or relay to CT ratio 200/5 so it displays the true line current.
Which load suits a 200/5A Encapsulated Square CT?
Choose it for circuits whose maximum running current is up to about 200A. On a 415V three-phase supply that is roughly 144 kVA. If the circuit normally runs well below that, a 100/5A CT gives better meter resolution; if it can exceed it, step up to 250/5A.
What are the accuracy class and burden of this Encapsulated Square CT?
It is supplied in Class 1.0 with a rated burden of 2.5-15 VA. Keep the total load of your meter and connecting leads within that burden to hold accuracy.
What busbar size fits the 32×10mm window?
The window is 32mm wide and 10mm high, so a busbar up to 32mm × 10mm including its insulation sleeve passes through. Send us your busbar size if you want us to confirm the fit.
Can I get a custom ratio, window size or a price?
Yes. Prices are on request. Use the Request Quote button or WhatsApp +91 78360 04040 with the ratio and quantity, and our sales desk will quote. Custom ratios, burdens and window sizes can be made on request.
Share Your Experience
Have you used our Current Transformers? Leave a verified review on Google.
Consistent ratio accuracy across all batches of CTs. Their busbar mounting brackets fit standard MCC panels without any fabrication adjustments. Excellent dispatch speed.
Best CT supplier in Delhi NCR. Polycarbonate casing is sturdy and terminal covers seal perfectly. GST invoice provided promptly with input tax credit.
We have been procuring ring CTs and tape-wound transformers from MVG Mangol Puri unit for over 3 years. Routine test reports are always provided with each lot.
Accurate Class 1.0 metering accuracy and great mechanical endurance. Tested with secondary injection test kit and ratio errors were well within specified limits.
Compare Nearby Ratios and Other CT Types
Not sure 200/5A is the right rating? Check the next ratio up or down, or the same rating in a different construction.