Resin Cast Ring Current Transformer - LTCT
LTCTs (low tension current transformers) in ring type resin cast construction for LTCT energy meters, LT panels and power monitoring. Ratios 60/5A to 1000/5A in 35, 45, 65 and 85mm round windows, Class 1.0 and 0.5 at 5, 10 or 15 VA, routine tested and dispatched from New Delhi.


100/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

150/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

200/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

250/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

300/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

400/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

500/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

600/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

800/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT

1000/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT
LTCT: Resin Cast Low Tension Current Transformers for LT Metering
MVG Power Solutions manufactures LTCTs (low tension current transformers) in ring type resin cast construction at Mangol Puri, New Delhi. An LTCT is also called a low voltage current transformer. Each low tension current transformer has its core and secondary winding fully cast in insulating resin, so the body is solid, moisture resistant and stable in hot, dusty LT panels. The primary cable or busbar passes through the round centre hole, and a transparent cover protects the secondary terminals.
These LTCTs feed LTCT energy meters, multifunction meters, ammeters and protection relays in LT distribution panels, building incomers, MCC and PCC panels, DG set panels and LTCT meter boxes. For loads below about 60A a whole-current meter is usually enough; above that, a CT-operated (LTCT) meter with the right ratio gives accurate readings.
Model Range and Dimensions
All models have a 5A secondary, are offered in Class 1.0 and Class 0.5 (0.5S on request) and carry model number 110*110-R-70. Width depends on the VA burden.
| Ratio | ID (mm) | OD (mm) | Width 5 VA | Width 10 VA | Width 15 VA | Class |
|---|---|---|---|---|---|---|
| 60/5A | 35 | 80 | 35 | 40 | 45 | 1.0 / 0.5 |
| 100/5A | 35 | 80 | 35 | 40 | 45 | 1.0 / 0.5 |
| 150/5A | 35 | 80 | 35 | 40 | 45 | 1.0 / 0.5 |
| 200/5A | 35 | 80 | 35 | 40 | 45 | 1.0 / 0.5 |
| 250/5A | 35 | 80 | 35 | 40 | 45 | 1.0 / 0.5 |
| 300/5A | 35 | 80 | 35 | 50 | 45 | 1.0 / 0.5 |
| 400/5A | 45 | 85 | 35 | 40 | 45 | 1.0 / 0.5 |
| 500/5A | 65 | 105 | 35 | 35 | 45 | 1.0 / 0.5 |
| 600/5A | 65 | 105 | 35 | 35 | 45 | 1.0 / 0.5 |
| 800/5A | 85 | 125 | 35 | 45 | 45 | 1.0 / 0.5 |
| 1000/5A | 85 | 125 | On request | 1.0 / 0.5 | ||
Electrical Parameters
- Rated secondary current: 5A
- Accuracy class: 1.0 or 0.5 (0.5S on request)
- Rated burden: 5, 10 or 15 VA
- Highest system voltage: 0.72 kV; power frequency withstand 3 kV for 1 minute
- Frequency: 50 Hz; insulation Class E
How to Choose the Right LTCT
Pick the ratio closest above your maximum running current, then the inner diameter that fits your cable or busbar. Choose Class 0.5 for billing or check metering and Class 1.0 for general monitoring, and keep the meter plus lead burden within the CT's VA rating. Our CT ratio guide, burden calculation guide and ring CT installation and polarity guide explain each step. Comparing constructions? See Encapsulated Ring CTs, Tape Wound Ring CTs and Plastic Ring CTs.
LTCT Frequently Asked Questions
What is an LTCT?
An LTCT is a low tension current transformer (also called a low voltage current transformer). Ours is a ring type CT whose core and winding are fully cast in insulating resin. The primary cable or busbar passes through the round centre hole, and the CT delivers a 5A secondary signal to energy meters, ammeters and relays on LT circuits up to 0.72 kV.
Which ratios and sizes are available?
Standard ratios run from 60/5A to 1000/5A in four inner diameters: 35mm (60-300A), 45mm (400A), 65mm (500-600A) and 85mm (800-1000A). Other ratios, dimensions and burdens can be made on request.
Which accuracy class and burden should I order?
Class 1.0 suits general panel metering; Class 0.5 suits billing, check metering and energy audits. Class 0.5S is available on request. Each class is offered at 5, 10 or 15 VA, and the CT width changes with the burden selected.
What is the difference between an LTCT and an HT CT?
An LTCT is insulated for low tension systems (0.72 kV highest system voltage) and is used in LT panels, meter boxes and distribution boards. HT CTs are built for 11 kV and above and are much larger. For 415V three-phase supplies, an LTCT is the correct choice.
What is the minimum order and how do I get a price?
The minimum order is 3 pieces per ratio. Prices are on request: send the ratio, ID, accuracy class, VA burden and quantity through the Request Quote button or on WhatsApp +91 78360 04040.