500/5A Plastic Ring Current Transformer | Class 1.0 Metering CT
| Ratio | 500/5A |
|---|---|
| Primary Current | 500A |
| Secondary Current | 5A |
| Accuracy Class | Class 1.0 |
| Window ID | 45mm |
| VA Rating | 2.5-15 VA |
| Construction | Plastic Ring Type Current Transformer |
| Application | Metering & Current Measurement |
500/5A Plastic Ring CT with 45mm Window: Specifications and Uses
The 500/5A Plastic Ring CT steps a primary current of 500A down to a 5A secondary signal (100:1) for ammeters, energy meters, power analysers and protection relays. A balanced three-phase load of 500A at 415V is about 359 kVA, so this rating suits circuits up to that size. It is supplied in Class 1.0 with a rated burden of 2.5-15 VA and a 45mm window.
Plastic Ring CT Construction and 45mm Window
The plastic ring construction uses an ultrasonic-welded ABS or polycarbonate body that keeps weight and cost down while protecting the core. The primary cable or conductor passes through the 45mm window, so there are no primary terminals to connect.
Where a 500/5A CT Is Used
At 500A, this CT is commonly specified for main incomers of distribution panels, large motors, capacitor (APFC) panels and plant section feeders. Panel builders and switchgear OEMs choose the plastic ring CT when the panel needs this rating in a 45mm window.
Accuracy, Burden and Testing
The CT delivers Class 1.0 accuracy within its rated burden of 2.5-15 VA, with marked primary (P1-P2) and secondary (S1-S2) terminals for correct polarity. The insulation level is 0.72 kV with a 3 kV, 1-minute power-frequency test. Each unit is routine tested for ratio error, phase displacement, insulation resistance and polarity before dispatch.
Supply and Dispatch
We manufacture at our factory in Mangol Puri, New Delhi, and dispatch across India with a GST invoice. For a quotation, send the ratio and quantity on WhatsApp +91 78360 04040 or use the Request Quote button.
What does a 500/5A ratio mean?
A 500/5A CT reduces a primary current of 500A to 5A on the secondary, a ratio of 100:1. Set the meter or relay to CT ratio 500/5 so it displays the true line current.
Which load suits a 500/5A Plastic Ring CT?
Choose it for circuits whose maximum running current is up to about 500A. On a 415V three-phase supply that is roughly 359 kVA. If the circuit normally runs well below that, a 400/5A CT gives better meter resolution; if it can exceed it, step up to 600/5A.
What are the accuracy class and burden of this Plastic Ring CT?
It is supplied in Class 1.0 with a rated burden of 2.5-15 VA. Keep the total load of your meter and connecting leads within that burden to hold accuracy.
What cable or busbar fits the 45mm window?
The 45mm opening takes insulated cable or a round conductor up to 45mm overall diameter. For a flat busbar, check that its width and thickness (with any sleeve) fit inside the opening, or send us the busbar size and we will confirm.
Can I get a custom ratio, window size or a price?
Yes. Prices are on request. Use the Request Quote button or WhatsApp +91 78360 04040 with the ratio and quantity, and our sales desk will quote. Custom ratios, burdens and window sizes can be made on request.
Share Your Experience
Have you used our Current Transformers? Leave a verified review on Google.
Consistent ratio accuracy across all batches of CTs. Their busbar mounting brackets fit standard MCC panels without any fabrication adjustments. Excellent dispatch speed.
Best CT supplier in Delhi NCR. Polycarbonate casing is sturdy and terminal covers seal perfectly. GST invoice provided promptly with input tax credit.
We have been procuring ring CTs and tape-wound transformers from MVG Mangol Puri unit for over 3 years. Routine test reports are always provided with each lot.
Accurate Class 1.0 metering accuracy and great mechanical endurance. Tested with secondary injection test kit and ratio errors were well within specified limits.
Compare Nearby Ratios and Other CT Types
Not sure 500/5A is the right rating? Check the next ratio up or down, or the same rating in a different construction.