500/5A Ring Resin Cast Current Transformer | Low Tension Current Transformer (LTCT) | Ring Resin Cast LTCT
| Current Ratio | 500/5A |
|---|---|
| Rated Primary Current | 500A |
| Rated Secondary Current | 5A |
| Accuracy Class | Class 1.0 / Class 0.5 (0.5S on request) |
| Rated Burden | 5 VA / 10 VA / 15 VA |
| Rated Frequency | 50 Hz |
| Highest System Voltage | 0.72 kV |
| Power Frequency Withstand | 3 kV for 1 minute |
| Insulation Class | Class E |
| Application | Metering & current measurement |
| Construction | Ring type, resin cast (low tension) |
|---|---|
| Inner Diameter (ID) | 65 mm, round |
| Outer Diameter (OD) | 105 mm |
| Width | 35 mm (5 VA) / 35 mm (10 VA) / 45 mm (15 VA) |
| Body Material | High-grade insulating cast resin |
| Terminal Cover | Transparent cover over secondary terminals |
| Polarity Marking | P1 / P2 primary, S1 / S2 secondary |
| Cooling | Dry type, air cooled |
| Mounting | Panel or busbar; cable or busbar passes through the centre hole |
| Model No. | 110*110-R-70 |
500/5A LTCT (65mm): Low Tension Current Transformer Specifications and Uses
The 500/5A LTCT is a ring type resin cast low tension current transformer, also known as a low voltage current transformer or CT coil. It steps a primary current of 500A down to a 5A secondary signal (100:1) for LTCT energy meters, ammeters, multifunction meters, power analysers and protection relays. A balanced three-phase load of 500A at 415V is about 359 kVA, so this rating suits LT circuits up to that size. It is offered in Class 1.0 and Class 0.5 (0.5S on request) at 5, 10 or 15 VA, with a 65mm round window.
Resin Cast Construction and 65mm Round Window
This resin cast ring type current transformer has its winding and core fully cast in high-grade insulating resin, giving a solid, moisture-resistant body that holds its shape in hot, dusty panels. The ring measures 65mm inside and 105mm outside, and its width depends on the burden: 35 mm (5 VA), 35 mm (10 VA), 45 mm (15 VA). The primary cable or busbar simply passes through the centre hole, and a transparent cover protects the S1-S2 secondary terminals.
Where a 500/5A LTCT Is Used
At 500A, this LTCT is commonly specified for main LT incomers on the low-voltage side of distribution transformers, PCC panels, busbar trunking take-offs and large industrial feeders. Electrical contractors, panel builders and switchgear OEMs choose the resin cast LTCT when they need a robust metering CT that installs without opening the primary circuit.
Accuracy Class, Burden and Testing
Choose Class 1.0 for general panel metering or Class 0.5 for billing and check metering. Keep the total load of the meter and connecting leads within the selected burden (5, 10 or 15 VA) to hold accuracy. The CT is rated for 0.72 kV highest system voltage with a 3 kV, 1-minute power-frequency withstand, Class E insulation and 50 Hz operation. Every unit is routine tested for ratio error, phase displacement, insulation resistance and polarity (P1-P2, S1-S2) before dispatch.
How to Order
Mention the ratio, inner diameter, accuracy class and VA burden when you order. The minimum order is 3 pieces, and we dispatch from Mangol Puri, New Delhi across India with a GST invoice. Not sure about the rating? Compare the 400/5A LTCT or 600/5A LTCT, see the full Resin Cast Ring LTCT range, or read our CT ratio selection guide and CT burden calculation guide. Download the LTCT product catalogue (PDF) (opens in new tab) for the full model range and dimensions.
What does a 500/5A LTCT ratio mean?
A 500/5A low tension current transformer reduces a primary current of 500A to 5A on the secondary, a ratio of 100:1. Set the energy meter or relay CT ratio to 500/5 so it shows the true line current.
Which load suits a 500/5A LTCT?
Choose it for circuits whose maximum running current is up to about 500A. On a 415V three-phase supply that is roughly 359 kVA. If the circuit normally runs well below that, a 400/5A LTCT gives better meter resolution; if it can exceed it, step up to 600/5A.
Should I choose Class 1.0 or Class 0.5?
Class 1.0 suits general panel metering and monitoring. Choose Class 0.5 for billing, check metering or energy audits where tighter accuracy is needed. Class 0.5S is available on request. Both classes are offered at 5, 10 and 15 VA.
What cable or busbar fits the 65mm window?
The 65mm round centre hole takes insulated cable or a round conductor up to 65mm overall diameter. For a flat busbar, check that its diagonal (with any sleeve) fits inside the opening, or send us the busbar size and we will confirm.
What is an LTCT and how do I get a price?
LTCT stands for Low Tension Current Transformer, also called a low voltage current transformer: a CT used on LT (up to 0.72 kV system voltage) circuits to feed meters and relays. Prices are on request: use the Request Quote button or WhatsApp +91 78360 04040 with the ratio, class, burden and quantity (minimum order 3 pieces).
Share Your Experience
Have you used our Current Transformers? Leave a verified review on Google.
Consistent ratio accuracy across all batches of CTs. Their busbar mounting brackets fit standard MCC panels without any fabrication adjustments. Excellent dispatch speed.
Best CT supplier in Delhi NCR. Polycarbonate casing is sturdy and terminal covers seal perfectly. GST invoice provided promptly with input tax credit.
We have been procuring ring CTs and tape-wound transformers from MVG Mangol Puri unit for over 3 years. Routine test reports are always provided with each lot.
Accurate Class 1.0 metering accuracy and great mechanical endurance. Tested with secondary injection test kit and ratio errors were well within specified limits.
Compare Nearby Ratios and Other CT Types
Not sure 500/5A is the right rating? Check the next ratio up or down, or the same rating in a different construction.