Current Transformer Accuracy Classes Explained: 0.2S, 0.5, 1.0 and 5P
The accuracy class printed on a CT, such as Class 1.0 or 0.5, is a promise about its maximum measurement error. This guide explains what the numbers mean, shows the limits for common metering classes, and says where each class is used.
What does the accuracy class mean?
For metering CTs the class number is the maximum percentage ratio error at rated current, at rated burden. A Class 1.0 CT is accurate to within ±1 percent at its rated primary current. The standards also set limits at lower currents, because a CT is less accurate when lightly loaded.
Error limits for common metering classes
These are the limits for the commonly used classes in the IEC CT standards. Check your product’s test certificate for the exact figures that apply to it.
| Class | At 5% current | At 20% current | At 100% to 120% current |
|---|---|---|---|
| 1.0 | ±3.0% | ±1.5% | ±1.0% |
| 0.5 | ±1.5% | ±0.75% | ±0.5% |
| 0.2S | ±0.35% (also ±0.75% at 1%) | ±0.2% | ±0.2% |
The “S” in 0.2S stands for special: the accuracy is held down to 1 percent of rated current, which matters for revenue meters on lightly loaded feeders.
Which class should you choose?
| Application | Typical class |
|---|---|
| Panel ammeters and indication | Class 1.0 or 3 |
| General energy monitoring, sub-metering | Class 1.0 |
| Commercial and industrial billing meters | Class 0.5 (check your utility requirement) |
| High-accuracy revenue metering | Class 0.2S (check your utility requirement) |
Class 1.0 CTs are the standard choice for panel metering and are listed on every product page, for example the 200/5A CT. For billing and check metering, our LTCTs are offered in Class 0.5 as standard (0.5S on request), for example the 200/5A LTCT and 400/5A LTCT. Other higher classes can be quoted on request; ask your meter supplier or utility which class they accept.
Metering CTs are not protection CTs
Protection classes such as 5P10 are defined differently. They guarantee accuracy at high fault currents, up to a multiple of rated current (10 times for 5P10), and are used with protection relays. A metering CT saturates early on purpose to protect the meter, so never use a Class 1.0 CT on a protection relay.
Accuracy depends on more than the class
- Burden: accuracy limits apply within the rated burden range (see CT burden calculation).
- Load level: readings at a few percent of rated current have larger errors, which is why a correctly chosen ratio matters (see how to choose the ratio).
- Installation: correct polarity and a single, well-centred conductor give the best results.
Frequently Asked Questions
What does Class 1.0 mean on a current transformer?
Class 1.0 means the ratio error is within plus or minus 1 percent at rated primary current and rated burden. The standards allow larger errors at lower currents, up to 3 percent at 5 percent of rated current.
Which accuracy class is used for energy billing?
Billing meters usually use Class 0.5 or 0.2S CTs, depending on the utility or tariff requirement. Confirm the class your supplier or utility specifies before ordering.
Can I use a metering CT with a protection relay?
No. A metering CT saturates at low overcurrent to protect the meter, so it will not reproduce fault current correctly. Use a protection-class CT such as 5P10 for relays.
What does the S in 0.2S stand for?
S means special. A Class 0.2S CT keeps its accuracy down to 1 percent of rated current, which suits revenue metering on feeders that are often lightly loaded.