How to Choose the Right Current Transformer Ratio (With Worked Examples)

A practical four-step method for choosing a CT ratio from 50/5A to 2500/5A, with load calculations for 415V three-phase panels.

The ratio is the first thing printed on a current transformer and the easiest to get wrong. A CT that is too small saturates and under-reads; one that is far too large gives coarse, inaccurate readings at normal load. This guide shows how panel builders and electricians pick the right ratio in four steps, with worked examples for a 415V three-phase system.

What does the CT ratio tell you?

New to current transformers? Our guide to what a CT coil is and how it works covers the basics.

A ratio such as 200/5A means the CT delivers 5A on its secondary when 200A flows through the primary conductor. That is a 40:1 current ratio. Your meter or relay needs this number set in its CT-ratio setting, so it multiplies the 5A it sees back up to the real line current.

Step 1: Find the maximum load current

For a three-phase supply the line current is:

I = kW × 1000 ÷ (√3 × V × power factor), or for a kVA rating, I = kVA × 1000 ÷ (√3 × V). At 415V this works out to roughly 1.39A per kVA.

LoadCalculated currentSuitable CT ratio
45 kW load at 0.9 power factor70 A75/5A or 100/5A
100 kW load at 0.9 power factor155 A200/5A
250 kVA feeder348 A400/5A
630 kVA transformer secondary876 A1000/5A

Step 2: Choose the nearest standard ratio at or above that current

CTs are made in standard ratios, so round up to the next one, not down. Many designers also leave 10 to 25 percent headroom so the CT does not need replacing when the load grows. The table shows the 415V three-phase load each standard ratio can carry, with a link to the ratios we list online.

CT ratioApprox. load at 415V, 3-phaseCurrent ratio
50/5A36 kVA10:1
60/5A43 kVA12:1
100/5A72 kVA20:1
150/5A108 kVA30:1
200/5A144 kVA40:1
250/5A180 kVA50:1
300/5A216 kVA60:1
400/5A288 kVA80:1
500/5A359 kVA100:1
600/5A431 kVA120:1
800/5A575 kVA160:1
1000/5A719 kVA200:1
1200/5A863 kVA240:1
1600/5A1150 kVA320:1
2000/5A1438 kVA400:1
2500/5A1797 kVA500:1

Need Class 0.5 for an LTCT energy meter or billing point? The same ratios up to 1000/5A are available as Resin Cast Ring Current Transformer - LTCT: 60/5A, 100/5A, 150/5A, 200/5A, 250/5A, 300/5A, 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A.

Step 3: Check the window

The conductor must pass through the CT window, including its insulation. A ring CT takes a cable or round conductor up to the window diameter, while flat busbars need a window wide and tall enough for the bar plus any sleeve. A square CT with a rectangular opening is usually the easiest fit for busbars; compare the options in our encapsulated ring, tape wound, square, plastic ring and LTCT (low tension current transformer) ranges.

Step 4: Match the burden and accuracy class

The meter plus the connecting leads must not exceed the CT’s rated burden (see our guide to CT burden calculation). Choose the class by the job: Class 1.0 for panel ammeters and general energy monitoring, a higher class where the reading is used for billing (see accuracy classes explained).

Common mistakes

  • Choosing too small: at overload the core can saturate and the meter under-reads exactly when the current is highest.
  • Choosing far too large: a 1000/5A CT on a circuit that normally carries 60A reads only a few percent of its range, where errors are larger.
  • Forgetting to set the meter: the CT ratio must be entered in the meter, otherwise it shows the 5A secondary value.
  • Using different ratios on the three phases: use identical CTs on all three phases of a three-phase meter.

Not sure which ratio suits your panel? Send us the load or feeder rating on WhatsApp and our team will confirm the right CT.

Frequently Asked Questions

How do I calculate the CT ratio for my load?

Calculate the maximum line current (kW divided by root three times voltage times power factor), then choose the nearest standard CT ratio at or above that current. For example, a 100 kW load at 0.9 power factor on 415V draws about 155A, so a 200/5A CT is the right choice.

Is it better to choose a larger CT ratio to be safe?

Only slightly. A modest margin of 10 to 25 percent is sensible, but a CT much larger than the load operates at a small fraction of its rating, where metering errors are bigger.

Do I need to set the CT ratio in the meter?

Yes. A meter with a 5A input must be told the CT ratio (for example 200/5) so it displays the true line current and power instead of the 5A secondary value.

Can I use different CT ratios on the three phases?

No. Use three identical CTs, with the same ratio, class and burden, on a three-phase meter.

Need help choosing? Contact our factory sales desk or message us on WhatsApp (+91 78360 04040) (opens in new tab).

Tags: #CT ratio selection #current transformer ratio #LT panel CT #CT sizing #CT manufacturer in Delhi
Share this Technical Guide

Help fellow switchgear engineers and electrical panel designers

Need CTs Built to These Technical Specifications?

Consult with our engineering team for custom current transformers and wholesale panel solutions.