CT Burden Explained: How to Calculate Burden and Choose the Right VA Rating
“Burden” is the electrical load connected to the CT secondary, measured in volt-amperes (VA). If the burden is higher than the CT is rated for, the CT loses accuracy. This guide explains how to add up the burden, with a worked example using real cable resistances.
What is CT burden?
At the rated secondary current of 5A, every ohm of resistance in the secondary circuit dissipates VA = I² × R, which is 25 × R. The CT must supply that power in addition to what the meter itself consumes. Our CTs are rated from 2.5 VA to 15 VA.
The burden formula
Total burden (VA) = meter burden + lead burden, where lead burden = 25 × (2 × one-way length × resistance per metre) for a 5A secondary. The factor of two is because current flows out and back through the leads.
Copper cable resistance
| Conductor size | Resistance at 20°C (ohm per km) |
|---|---|
| 1.5 mm² | 12.1 |
| 2.5 mm² | 7.41 |
| 4 mm² | 4.61 |
| 6 mm² | 3.08 |
Worked example
A digital meter drawing 1 VA sits 10 m from the CT. Compare two cable sizes:
| Cable | Loop resistance | Lead burden | Total with meter |
|---|---|---|---|
| 1.5 mm² | 2 × 10 × 0.0121 = 0.242 Ω | 25 × 0.242 = 6.05 VA | 7.05 VA |
| 2.5 mm² | 2 × 10 × 0.00741 = 0.148 Ω | 25 × 0.148 = 3.71 VA | 4.71 VA |
With 1.5 mm² wire the total of about 7 VA would overload a 5 VA CT. Using 2.5 mm² brings it to about 4.7 VA, which a 5 VA CT can handle, though a 10 VA CT leaves more margin.
How to bring the burden down
- Use thicker secondary cable. Moving from 1.5 to 2.5 mm² cuts the lead burden by about 40 percent.
- Shorten the run. Mount the meter close to the CT where the layout allows.
- Choose a 1A secondary. Lead burden falls with the square of the current, so a 1A secondary has 25 times less lead burden than 5A. Ask us for a 1A CT where runs are long.
- Select a higher VA rating. Choose a CT whose rated burden comfortably exceeds your total. For example, the 300/5A LTCT is offered at 5, 10 or 15 VA.
Is a lower burden always better?
Not quite. CT accuracy limits are normally specified between 25 and 100 percent of rated burden. A 15 VA CT connected to a 1 VA meter is outside that range, so match the rated VA to the real load instead of simply choosing the highest value. See the full range in our encapsulated ring CTs or tape wound CTs, or choose a LTCT, offered at 5, 10 and 15 VA.
Related reading: how to choose a CT ratio and CT accuracy classes.
Frequently Asked Questions
What is burden in a current transformer?
Burden is the load connected to the CT secondary, expressed in VA. It includes the meter or relay plus the resistance of the connecting leads, and it must not exceed the CT rated burden.
How do I calculate lead burden for a 5A secondary?
Lead burden in VA equals 25 times the loop resistance of the leads in ohms. The loop is twice the one-way cable length, because current goes out and returns.
Why would I choose a 1A secondary instead of 5A?
Lead burden varies with the square of the current, so a 1A secondary has one twenty-fifth of the lead burden of a 5A secondary. This helps when the meter is a long way from the CT.
What happens if the burden is too high?
The CT core can saturate and the ratio error grows, so the meter under-reads. Reduce the burden with thicker cable, a shorter run, a 1A secondary or a CT with a higher VA rating.