What Is a CT Coil? Types, Ratios and Price Guide for Indian Panels

A CT coil is a current transformer. Learn how it works, how to read ratios like 100/5, which type suits your panel and what decides CT coil price.

Ask an electrician in India for a current transformer and they will usually call it a CT coil. It is one of the cheapest parts in an electrical panel, yet a wrong ratio or burden makes every energy meter reading on that feeder wrong.

This guide explains what a CT coil is, how to read ratios like 100/5, which type suits your panel, what decides CT coil price, and how to order the right one the first time.

What Is a CT Coil?

A CT coil is a current transformer: an instrument transformer that reduces a high primary current to a small, standard secondary current, usually 5A (sometimes 1A). Meters, ammeters and relays are built for that small current, so the CT lets them measure 100A, 400A or 2000A safely.

The main cable or busbar passes through the CT window and acts as the primary. The secondary winding, wound on a ring or square core, delivers a current proportional to the load to terminals marked S1 and S2.

How a CT coil works

  • Load current flows through the primary conductor (P1 to P2).
  • The core carries the magnetic flux created by that current.
  • The secondary winding produces a scaled-down current, for example 5A when the full rated current flows.
  • The meter, set to the same ratio, multiplies the reading back to the true line current.

Safety rule: never open the secondary (S1-S2) of a CT while current flows in the primary. An open secondary can develop dangerous voltages. Short the secondary before disconnecting a meter. See our ring CT installation and polarity guide.

CT Coil Ratios Explained (100/5, 200/5 and More)

The ratio printed on a CT coil tells you the primary current that produces the full 5A secondary.

CT coil ratioTurns ratioApprox. 3-phase load at 415VTypical use
50/5A10:136 kVASmall shops, sub-metering
100/5A20:172 kVASmall commercial LT metering
200/5A40:1144 kVABuilding incomers, MCC feeders
400/5A80:1288 kVALT distribution panels
800/5A160:1575 kVALarge feeders
1600/5A320:11150 kVAMain LT incomers

Reading a 100/5 CT coil

A 100/5 CT coil gives 5A on the secondary when 100A flows in the primary, a 20:1 ratio. At 50A load it gives 2.5A. Set the meter's CT ratio to 100/5 so it displays 50A, not 2.5A.

How to pick the ratio

  1. Find the maximum running current of the feeder.
  2. Choose the nearest standard ratio at or above that current.
  3. Avoid going far above it: a 1000/5 CT on a 60A load reads only a few percent of its range, where accuracy is poorest.

Worked examples are in how to choose a CT ratio.

Types of CT Coil and Where Each One Fits

The core and secondary are similar in every type. The housing and window shape decide where each one fits best.

TypeWindowBest forTypical ratios
Encapsulated ring CTRoundRugged cable metering, DG sets, incomers50/5A to 2500/5A
Encapsulated square CTBusbar slot + round holeFlat copper or aluminium busbars50/5A to 1000/5A
Tape wound ring CTRoundCompact, low-cost OEM panels60/5A to 600/5A
Plastic ring CTRoundLight sub-metering in compact boards30/5A to 600/5A
Resin Cast Ring Current Transformer - LTCTRoundLTCT energy meters, Class 0.5 billing60/5A to 1000/5A

Encapsulated ring and square CT coils

Encapsulated CTs are sealed in a moulded body, so they handle dust, vibration and site handling well. Choose an encapsulated ring CT for round cables and an encapsulated square CT when the conductor is a flat busbar.

Tape wound and plastic ring CT coils

Tape wound ring CTs and plastic ring CTs are lighter and lower in cost, which is why OEM panel builders and DG set makers buy them in volume. They suit protected positions inside a panel. Compare them in ring CT vs tape wound CT vs square CT.

LTCT (low tension current transformer)

An LTCT is a CT coil insulated for low tension systems (0.72 kV) and used with CT-operated energy meters, often called LTCT meters. Resin cast LTCTs in Class 0.5, such as the 200/5A LTCT, are common where the reading is used for billing or check metering. See the full Resin Cast Ring Current Transformer - LTCT range.

Accuracy Class and Burden: The Two Specs Most Buyers Miss

Accuracy class

  • Class 1.0: panel ammeters, general energy monitoring, sub-metering.
  • Class 0.5: commercial and industrial billing or check metering.
  • Class 0.2S / 0.5S: high-accuracy revenue metering where the utility asks for it.

Always confirm the class your utility or meter supplier accepts. More in CT accuracy classes explained.

Burden (VA rating)

Burden is the total load on the CT secondary: the meter plus the resistance of the connecting leads. If it exceeds the CT's VA rating, accuracy falls. Long lead runs on 1.5 mm² cable are the most common cause.

  • Use 2.5 mm² copper or larger for the CT secondary.
  • Keep the meter close to the CT where possible.
  • For long runs, ask for a 1A secondary.

See the CT burden calculation guide for a worked example.

What Decides CT Coil Price?

Buyers often search for a current transformer price list, but two CT coils with the same ratio can differ in price. These factors set the price:

  1. Ratio and window size: larger windows and higher ratios need more core material.
  2. Construction: encapsulated and resin cast bodies cost more than tape wound or plastic ring types.
  3. Accuracy class: Class 0.5 or 0.2S needs a better core than Class 1.0.
  4. Burden: higher VA ratings need a larger core.
  5. Secondary current: 1A secondaries need more turns.
  6. Quantity: per-piece prices fall at panel-builder and OEM volumes.
  7. Testing and documents: routine test reports and certificates add value for utility and project jobs.

A cheap CT coil that saturates or drifts costs more in wrong billing than it saves. Buy from a current transformer manufacturer in India that routine tests every unit for ratio error, phase displacement, insulation and polarity. CT coils are commonly classified under HSN heading 8504 (transformers); confirm the exact HSN code and GST rate with your accountant for your invoice.

How to Order the Right CT Coil

Send these details with every enquiry and you will get an accurate quote quickly:

  1. Ratio, for example 200/5A.
  2. Window: cable diameter or busbar width x thickness.
  3. Type: ring, square, tape wound, plastic or LTCT.
  4. Accuracy class: 1.0, 0.5 or 0.5S.
  5. Burden: 2.5, 5, 10 or 15 VA.
  6. Secondary current: 5A or 1A.
  7. Quantity: one CT per phase, so three for a three-phase four-wire meter (see how many CTs for a three-phase meter).

Frequently Asked Questions

What is a CT coil used for?

A CT coil (current transformer) lets meters, ammeters and relays measure high currents safely. It reduces the line current to a standard 5A or 1A secondary that the instrument is designed for.

What does a 100/5 CT coil mean?

It gives 5A on the secondary when 100A flows through the primary, a 20:1 ratio. Set the meter's CT ratio to 100/5 so it shows the true current.

What is the price of a CT coil?

It depends on ratio, window size, construction, accuracy class, burden and quantity. Manufacturers quote on request; share the ratio, type, class, burden and quantity for an exact price.

What is the difference between a CT coil and an LTCT?

LTCT is a CT coil insulated for low tension (up to 0.72 kV) systems and used with CT-operated energy meters. Every LTCT is a CT coil, but the term is mostly used for metering CTs in LT panels and meter boxes.

Can I use a 5A CT coil with any energy meter?

Only if the meter is a CT-operated meter with a 5A (-/5A) current input and you set the matching ratio in the meter. Whole-current meters connect directly to the load and do not use a CT.

Conclusion

A CT coil is a small part with a big effect on metering accuracy. Choose the nearest ratio above your load, match the window to the conductor, pick the class your application needs, and keep the burden within the CT's VA rating.

MVG Power Solutions manufactures and routine tests ring, square, tape wound, plastic ring and resin cast LTCT coils in New Delhi, from 30/5A to 2500/5A. Send your ratio and quantity on WhatsApp (+91 78360 04040) (opens in new tab) for a quotation, or browse all current transformer collections.

Tags: #CT coil #CT coil price #CT coil 100/5 #current transformer #LTCT #CT manufacturer in India